Gas burner compliant with European standard EN676. Electronic modulation
72 h continuous operation, optional
Modulation ratio 1:5
Gas burner with low NOx and CO emissions in accordance with European standard EN676: class 4
Adjusting the combustion head.
Combustion air intake with throttle damper. Air flow adjustment with electric servomotor.
Fully closing air damper on shutdown to avoid loss of heat through the chimney.
Maintenance facilitated by the possibility of removing the combustion head without having to remove the burner from the boiler.
Fixed boiler coupling flange.
Easy maintenance thanks to the two-sides hinge which allows the removal of the combustion head without having to remove the burner from the boiler.
Device made of sound-absorbing material to reduce fan noise.
CE version gas train is complete with operation and safety valve with electromagnetic drive, maximum and minimum pressure switch with gas leakage control, pressure regulator and gas filter
Fail proof connectors for burner/gas train connection
Gas train exit: high/low.
Flame detection by ionisation electrode with connector for micro amp meter.
Control panel equipped either with display showing the working process and with the keyboard for the burner adjustment.